TEL. & FAX +66(0)2-020-3301

IMC-101G Series

Home  >   MOXA  >   Industrial Network Infrastructure  >  
Ethernet Media Converters

Industrial Gigabit Ethernet-to-fiber media converter

Product Feature

  • 10/100/1000BaseT(X) and 1000BaseSFP slot supported
  • Link Fault Pass-Through (LFPT)
  • Power failure, port break alarm by relay output
  • Redundant power inputs
  • -40 to 75°C operating temperature range (-T models)
  • Designed for hazardous locations (Class 1 Div. 2/Zone 2, IECEx)
  • More than 20 options available

Introduction

The IMC-101G industrial Gigabit modular media converters are designed to provide reliable and stable 10/100/1000BaseT(X)-to-1000BaseSX/LX/LHX/ZX media conversion in harsh industrial environments. The IMC-101G’s industrial design is excellent for keeping your industrial automation applications running continuously, and each IMC-101G converter comes with a relay output warning alarm to help prevent damage and loss. All IMC-101G models are subjected to a 100% burn-in test, and they support a standard operating temperature range of 0 to 60°C and an extended operating temperature range of -40 to 75°C.

Ethernet Interface

10/100/1000BaseT(X) Ports 
(RJ45 connector)
1
1000 Mbps fiber (SFP 
connector)
1
Magnetic Isolation Protection1.5 kV (built-in)

Power Parameters

Input Current200 mA @ 12 to 45 VDC
Input Voltage12 to 45 VDC
Overload Current ProtectionSupported
Power ConnectorTerminal block
Power Consumption200 mA @ 12 to 45 VDC

Physical Characteristics

HousingMetal
Dimensions53.6 x 135 x 105 mm (2.11 x 5.31 x 4.13 in)
Weight630 g (1.39 lb)
InstallationDIN-rail mounting

Environmental Limits

Operating TemperatureStandard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature (package
included)
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity5 to 95% (non-condensing)

Standards and Certifications

EMCEN 55032/24
EMICISPR 32, FCC Part 15B Class A
EMSIEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
IEC 61000-4-8 PFMF
IEC 61000-4-11
Environmental TestingIEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-3
SafetyEN 60950-1, UL 60950-1
VibrationIEC 60068-2-6
Hazardous LocationsStandard models: UL/cUL Class I Division 2 Groups A/B/C/D
-IEX models: UL/cUL Class I Division 2 Groups A/B/C/D, ATEX Zone 2, IECEx

MTBF

Time500,540 hrs
StandardsTelcordia (Bellcore), GB

Warranty

Warranty Period5 years
DetailsSee www.moxa.com/warranty
Name Type Version Release Date
Datasheet for IMC-101G Series Datasheet V1.5 21 May 2020

IMC-101G

Operating Temp. 0 to 60°C
IECEx Supported

IMC-101G-T

Operating Temp. -40 to 75°C
IECEx Supported

IMC-101G-IEX

Operating Temp. 0 to 60°C
IECEx Supported

IMC-101G-T-IEX

Operating Temp. -40 to 75°C
IECEx Supported

Notice: Undefined variable: rs5 in /opt/lampp/htdocs/productview.php on line 633

Notice: Trying to get property 'tab_ap' of non-object in /opt/lampp/htdocs/productview.php on line 633


Notice: Undefined variable: title_ap in /opt/lampp/htdocs/productview.php on line 638


Notice: Undefined variable: detail_ap in /opt/lampp/htdocs/productview.php on line 639

บริษัท พีที ออโตเมชั่น (ไทยแลนด์) จำกัด

  • เลขที่ 9 อาคารภคินท์ ชั้น 9 ห้องเลขที่ 901 ถนนรัชดาภิเษก แขวงดินแดง เขตดินแดง กรุงเทพฯ 10400
  • โทรและแฟกซ์ : +66(0)-2020-3000
  • อีเมล์ : [email protected]
  • Facebook : facebook.com/ptautomations

จันทร์ ถึง ศุกร์ เวลา 9.00 น. – 18.00 น.

EN
TH